Main specifications
| |
Specifications |
| Model name |
DTA113B51 |
| Supply-Voltage |
DC 16 V supplied from R/C line |
| Maximum number of connectable indoor units |
4 units per adapter PCB, 40 units when 10 adapters are connected |
| Forced on/off input |
Non-voltage (normal) 'a' contact 2 Each
point |
| Dimensions |
100 x 100 x 35 [mm] |
| Method of installation |
Built into indoor unit or placed inside a box especially built for it |
| Communications functions |
RS232C, support for AT modem |
| Ambient temperature/humidity conditions for operation |
-10 to +50 ,
Max. of 95%RH |
| Control functions |
on/off, Operation mode, Temperature setting, Airflow direction, Airflow rate, Filter sign reset |
| Monitoring functions |
on/off, Operation mode, Temperature setting, Airflow direction, Airflow rate, Filter sign |
| Malfunction monitoring functions |
Malfunction reporting function |
| Automatic alternating operation function |
Yes |
| Backup operation function |
Yes |
|
Overseas standards compatibility
 |
Safety standards: IEC60730 |
 |
EMC standards: CISPR22-A (EMI), CISPR-24 (EMS) |
Model variations
 |
DS-NET adapter (DTA113B51) |
 |
Monitoring panel software (DPC001B51) |
|
Applicable models
| Indoor unit |
Installation box for adaptor |
| FA-F |
- |
| FAY-F |
- |
| FAY-FA |
- |
| FAYP-B |
- |
| FHK-F |
- |
| FHYK-FJ |
- |
| FH(Y)B-F |
KRP1B97 |
| FHB-F |
KRP1B97 |
| FAY-L |
KRP4A93 |
| FH(Y)-B |
KRP1C93 |
| FHYP-B |
KRP1C93 |
| FV(Y)-LA |
KRP4A95 |
| FFQ-BV1B |
KRP1B101 |
| FUY-FJ |
KRP1B97 |
| FUYP-B |
KRP1B97 |
| FH(Y)C-K |
KRP1B98 |
| FHYCP-D |
KRP1D98 |
|
|
Notes
| 1. |
A remote controller is required for each indoor unit that is connected to this adaptor. |
| 2. |
If this adaptor is attached, dual remote controller operation is not possible. Also, combined use with a wireless remote controller is not possible. |
| 3. |
Combined use with centralized remote controllers, an intelligent Touch Controller,
BACnet Gateway, and a group distance control adaptor is not possible. |
| 4. |
This adaptor is compatible with a wide range of indoor units that are equipped with remote controller wiring, However, in some cases an installation box or installation board will be required. (Four power cables with different lengths are included in the package.) |
| 5. |
Network equipment,an AT modem as specified above, etc.,will be necessary to connect to the lnternet. |
| Note that it may not be possible to install the system
due to the condition of the telephone line. |
|
|
|
 |