Connection unit
Connection unit is the device for connecting above indoor unit to VRV III and VRV II systems.
*1.
| Model |
Maximum piping length between the BEV unit and the indoor unit. |
| FXUQ-MAV1 |
5 m |
|
Notes:
- • When connecting centralised-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52).
- • Connection unit BEVQ-MA is necessary for each indoor unit.
- • The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m.
- • The BEV unit must be installed within a maximum height difference between indoor units of 15 m.
- • Branching of the refrigerant piping is not possible downstream of the BEV unit.