Using a single system
Air conditioning and outdoor air processing can be accomplished using a single system.
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
- When outdoor-air processing units are connected, the total connection capacity must be within 50% to 100% of that of the outdoor units.
- When outdoor-air processing units and standard indoor units are connected, the total connection capacity of the outdoor-air processing units must not exceed 30% of that of the outdoor units.
- Outdoor-air processing units can be used without indoor units.
- Connectable outdoor units: VRV II and III systems.