Using a single system
Air conditioning and outdoor air processing can be accomplished using a single system.
Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
- The total connected capacity of the standard indoor units and outdoor-air processing units must be between 50% and 100% of the capacity of outdoor units. The connected capacity of the outdoor-air processing unit must not exceed 30% of the capacity of outdoor units.
- An outdoor-air processing unit can be used exclusively. The connected capacity of the outdoor-air processing unit must be between 50% and 100% of the capacity of outdoor units.
- Connectable outdoor units: VRV II and III systems
System Example
Check to make sure that your system's connected capacity is within the appropriate range.
- Total connected capacity of standard indoor units and outdoor-air processing unit does not exceed 100%. OK, because system capacity of 20 HP = indoor unit capacity of 20 HP.
- Connected capacity of outdoor-air processing unit does not exceed 30% of this. OK, because system capacity of 20 HP x 0.3 = 6 HP > outdoor-air processing unit capacity of 5 HP.