Enhanced comfort
Outdoor units designed for low-noise operation
Outdoor units created with cutting-edge technologies provide quiet operation to increase users' comfort.
Nighttime quiet operation function
Operation sound level selectable from 3 steps for the night mode.
Mode 1. Automatic mode
Time of maximum temperature is memorised. The low operating mode will become active 8 hours*2 after the peak temperature in the daytime, and operation will return to normal 10 hours*3 after that. The operation sound level for the night mode can be selected from 55 dB (Step 1), 50 dB (Step 2) and 45 dB (Step 3). (For a single outdoor unit.)
Note:
- • This function is available in setting at site.
- • The relationship of outdoor temperature (load) and time shown in the graph is just an example.
- * The capacity reduction rate differs depending on the operation sound level step selected.
Mode 2. Manual mode
Starting time and ending time can be input.*4
Mode 3. Combined mode
Combination of mode 1 and 2 can be used depending on your needs.
- *1. Determine which mode to select depending on the climatic characteristics of each country.
- *2. Initial setting. Can be selected from 6, 8 and 10 hours.
- *3. Initial setting. Can be selected from 8, 9 and 10 hours.
- *4. External control adaptor for outdoor unit, DTA104A61 or DTA104A62, and a subsequently obtained timer are necessary.